Supply Voltage Insufficient
The switch-mode power supply output voltage has dropped below the specified regulation range, typically below 90% of nominal output voltage. This condition affects the PFC stage boost converter or main transformer regulation, causing inadequate power delivery to connected industrial equipment and potential system instability.
Error Code
E7928
Severity
Warning
Equipment
Power Supply
Manufacturer
Bosch Rexroth
Output voltage measured 15-20% below nameplate rating using calibrated DMM
Yellow or amber fault LED illuminated on power supply front panel
Connected equipment experiencing intermittent resets or brownout conditions
Output ripple voltage exceeds 5% of DC output when measured with oscilloscope
Power supply cooling fans running at maximum speed continuously
Audible high-frequency whining or whistling from transformer core
Aging electrolytic capacitors in output filter stage with ESR above 100 milliohms
Faulty feedback optocoupler providing incorrect voltage reference to control IC
Degraded PFC boost inductor with partial winding short reducing power factor correction
Main transformer primary or secondary winding resistance increased due to thermal stress
Control IC switching frequency drift caused by internal oscillator component failure
Input filter capacitor failure causing poor power factor and voltage regulation
Perform lockout/tagout procedure and verify zero energy state with calibrated voltage tester
Measure output voltages under no-load and full-load conditions using precision DMM
Test all electrolytic capacitors with ESR meter, replace any with ESR >100mΩ or <80% rated capacitance
Check feedback optocoupler CTR using curve tracer, replace if below 50% of original specification
Measure PFC inductor DC resistance and compare to nameplate value, replace if >110% of specification
Verify control IC switching frequency at pin 4 using oscilloscope, replace IC if frequency drift >±5%
Apply rated load and verify output voltage regulation within ±2% over 30-minute thermal cycle test
Safety First: Always isolate power and follow LOTO (Lockout/Tagout) procedures before working on electrical components. If unsure, contact a certified repair technician.
Get fault code alerts for Bosch Rexroth equipment
Weekly repair tips, new fault codes, maintenance guides — free.
Other Bosch Rexroth Fault Codes
View all →Get Your Equipment
Back in Action — Fast
Send us your faulty industrial electronics. Our engineers will diagnose it and provide a detailed quote within 24 hours — with no obligation to proceed.
Free Evaluation
No obligation
48hr Turnaround
Fastest in India
6-Month Warranty
Every repair
No Fix, No Charge
Zero risk policy
Pan-India Pickup
Doorstep service