🔴 FaultSiemensSoft Starter⚠️ Professional Repair Required
F1073

DC Link Overvoltage

The DC link capacitor voltage exceeds critical protection limits, typically above 850VDC, due to regenerative energy from decelerating motor loads or supply transients. This fault immediately disables SCR firing circuits and activates crowbar protection to prevent catastrophic component failure.

Quick Reference

Error Code

F1073

Severity

Fault

Equipment

Soft Starter

Manufacturer

Siemens

Observable Symptoms6 indicators
#1

Red FAULT LED solid with alternating display showing 'OV' and fault code E45

#2

Immediate motor shutdown with bypass contactor forced open regardless of run command

#3

Oscilloscope shows DC link voltage spikes >850VDC with poor regulation during transients

#4

Audible high-frequency switching noise from crowbar circuit activation

#5

Ground fault indicator may activate due to stress on insulation systems

#6

SCR gate driver outputs disabled showing 0V at gate terminals G1-G6

Root Cause AnalysisMost common first
Most Likely

Motor deceleration too rapid causing regenerative energy feedback through SCRs

90%
Common

Failed DC link capacitor allowing voltage ripple and regulation loss

70%
Possible

Lightning or switching transients exceeding varistor clamping capability

50%
Less Common

Defective crowbar SCR not conducting when triggered above 820VDC threshold

35%
Less Common

Open circuit in DC link discharge resistor preventing controlled voltage decay

20%
Less Common

Control PCB overvoltage detection circuit false triggering due to noise

20%
Step-by-Step Repair Procedure7 steps — safe checks first
Repair Progress Tracker0 / 7 steps
1

Establish electrical safety boundary and verify equipment isolation using Category IV rated test equipment

2

Discharge DC link capacitors through 10kΩ resistor until voltage reads <50VDC using isolated probe

3

Test DC link capacitor bank with capacitance analyzer expecting values within ±15% of 2200µF nominal

4

Verify crowbar SCR triggering at 820VDC using controlled DC supply and oscilloscope monitoring

5

Check discharge resistor continuity expecting 47kΩ ±5% resistance across R22 terminals

6

Replace varistor surge suppressors MOV1-MOV3 if leakage current exceeds 1mA at rated voltage

7

Validate complete protection system with high-voltage transient test confirming trip at 850VDC ±2%

⚠️

Safety First: Always isolate power and follow LOTO (Lockout/Tagout) procedures before working on electrical components. If unsure, contact a certified repair technician.

Affected Equipment Models
SIRIUS 3RW30SIRIUS 3RW40SIRIUS 3RW44SIKOSTART 3RW22SIRIUS 3RW52SIRIUS 3RW31
🔔

Get fault code alerts for Siemens equipment

Weekly repair tips, new fault codes, maintenance guides — free.

Trusted Since 1994 · ISO Certified · 32+ Years

Get Your Equipment
Back in Action — Fast

Send us your faulty industrial electronics. Our engineers will diagnose it and provide a detailed quote within 24 hours — with no obligation to proceed.

Free Evaluation

No obligation

48hr Turnaround

Fastest in India

🛡

6-Month Warranty

Every repair

No Fix, No Charge

Zero risk policy

📦

Pan-India Pickup

Doorstep service