Skip to main content
OPEN NOW
0s

0% of today's working hours elapsed

Office Hours (IST)

Mon – Fri9:00 AM – 6:00 PM
Saturday9:00 AM – 3:00 PM
SundayClosed
Track Repair →
🔴 FaultSchneider ElectricAC Drive / VFD⚠️ Professional Repair Required
108

Phase Imbalance

The three-phase input power supply exhibits significant voltage or current imbalance exceeding 2-3% tolerance, causing uneven loading of the input rectifier diodes and DC bus ripple. This condition leads to increased component stress, overheating, and potential drive shutdown to prevent damage to power semiconductors and capacitors.

Quick Reference

Error Code

108

Severity

Fault

Equipment

AC Drive / VFD

Manufacturer

Schneider Electric

Observable Symptoms6 indicators
#1

Yellow PHASE or IMBAL LED indicator active on front panel

#2

Fault code F006 or PH displaying voltage imbalance percentage

#3

Motor exhibits increased vibration and audible noise during operation

#4

Individual phase currents vary by more than 5-8% between phases

#5

DC bus ripple voltage exceeds 10% of average value

#6

Drive randomly trips during high load conditions

Root Cause AnalysisMost common first
Most Likely

Loose or corroded input terminal connections causing voltage drops

90%
Common

Failed input fuse or contactor contact creating single-phase operation

70%
Possible

Unbalanced utility supply with phase-to-phase voltage differences exceeding 2%

50%
Less Common

Motor winding fault creating unequal impedance between phases

35%
Less Common

Worn or damaged input reactor with asymmetrical inductance values

20%
Less Common

Defective input rectifier diode causing uneven current distribution

20%
Step-by-Step Repair Procedure7 steps — safe checks first
Repair Progress Tracker0 / 7 steps
1

Execute lockout/tagout and verify all energy sources are isolated safely

2

Measure and record all three phase-to-phase voltages with precision multimeter

3

Check input terminal tightness to manufacturer torque specifications

4

Test input fuses for continuity and proper current ratings

5

Verify motor winding resistance balance within 2% using milliohm meter

6

Replace any failed rectifier diodes after confirming proper gate driver operation

7

Perform complete phase balance verification test under full rated load conditions

⚠️

Safety First: Always isolate power and follow LOTO (Lockout/Tagout) procedures before working on electrical components. If unsure, contact a certified repair technician.

Affected Equipment Models
ATV12ATV32ATV320ATV630ATV930ATV71
🔔

Get fault code alerts for Schneider Electric equipment

Weekly repair tips, new fault codes, maintenance guides — free.

Trusted Since 1994 · ISO Certified · 32+ Years

Get Your Equipment
Back in Action — Fast

Send us your faulty industrial electronics. Our engineers will diagnose it and provide a detailed quote within 24 hours — with no obligation to proceed.

Free Evaluation

No obligation

48hr Turnaround

Fastest in India

🛡

6-Month Warranty

Every repair

No Fix, No Charge

Zero risk policy

📦

Pan-India Pickup

Doorstep service